
Configuration level
Configuration parameters 38 KS 90-1p / KS 92-1p
Name Value range Description Default
Err.r
Reset of all error list entries
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
6
Ò - key switches
Pid.2
Switching of parameter set (Pb, ti, td)
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
P.run
Programmer-Run/Stop (see Page xx)
0
0
no function
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
P.off
Programmer off. Internal set-point is effective (see Page xx)
0
0
no function
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
I.Chg
Switching of the actual process value between Inp1 and X2
0
0
no function (switch-over via interface is possible)
2
DI1 switches
3
DI2 switches (only visible with OPTION)
4
DI3 switches (only visible with OPTION)
5
è - key switches
di.Fn
Function of digital inputs (valid for all inputs)
0
0
direct
1
inverse
2
toggle key function
fDI1
fDI2
fDI3
Forcing di1/di2/di3 (only visible with BlueControl!)
0
0
No forcing
1
Forcing via serial interface
q
othr
Name Value range Description Default
bAud
Baudrate of the interface (only visible with OPTION)
2
0
2400 Baud
1
4800 Baud
2
9600 Baud
3
19200 Baud
Addr
1...247
Address on the interace (only visible with OPTION)
1
Commenti su questo manuale